← Passive Fire Protection
Firebreather® Cavity Barrier
Flamro

Firebreather® Cavity Barrier

Open-state fire barrier for ventilated building façades — stainless steel mesh with intumescent tape that seals immediately in a fire, with certified EI 30 or EI 60 fire resistance.

Choose Capacity

Download Technical Datasheet (PDF)
Technical Specifications
CategoryPassive Fire Protection
BrandFlamro
System Test StandardsBS 8414, SP FIRE 105, Lepir 2, NFPA 285
CertificationETA-25/0626, RISE RISEFR 010-0238, CSTB AL16-182, Certificate of Conformity ESL-24-11693
TechnologyFirebreather® (Flamro)
MaintenanceNo periodic inspection or maintenance required
Tape compositionHalogen-free intumescent material based on expandable graphite
Reaction Onset Temperature~175°C
PropertiesPassive system with no moving parts, no PVC/plastic; blocks sparks and birds/rodents/insects larger than 2 mm, allows ventilation until it expands
Expansion pressure0,6 – 1,3 N/mm² (300°C)
Length1130mm
Height112 mm (tolerance ±7 mm)
ApplicationOpen-state fire barrier behind ventilated façades or other cavities with fire protection requirements
Intumescent Tape CertificationETA-15/0719
StorageDry place
Product CodesFBH-23-1130-30 (EI30), FBH-23-1130-60 (EI60)
ClassificationEI 30 / EI 60 / EI 90 per EN 13501-2 (depending on the material behind the façade)
Expected Service Life60 years (per ASTM E2923-14)
Product Test StandardsEN 1366-4, pr-EN 1364-6, ASTM E2912, TGD 19
Intumescent TapeKERAFIX® Flexpan 200 NG-A — intumescent graphite material, halogen-free
Available Fire Resistance ClassesEI 30, EI 60
Mesh MaterialAISI304 stainless steel, wire diameter 0.56 mm, mesh opening 2 mm
Gap Width23 mm (tolerance +4 mm)
Environmental Product Declaration (EPD)NEPD-5507-4806-EN
Expansion Ratio22–37 times