← Fire Break
FIREBREAK 66 INTUMESCENT PRESSURE SEALANT
Fire Break

FIREBREAK 66 INTUMESCENT PRESSURE SEALANT

Firebreak 66 is a one part intumescent acrylic sealant which in fire conditions expands with high pressure to seal openings in fire compartmenting structure when penetrated by plastic pipes, metal pipes with combustible insulation and single or bunched cables. Description Firebreak 66 is a halogen-free, polymer emulsion-based sealant designed to maintain the fire resistance of floor and walls when penetrated by plastic pipes and metal pipes with continuous combustible insulation. Under fire conditions the intumescent filler expands to many times its original thickness exerting pressure on the softening pipe and/or insulation closing the opening with a dense block of fire resistant char that restricts the passage of smoke and fire. Fire testing has been conducted in conjunction with a range of pipe and cable service penetrations through fire compartmenting floors and walls including 100mm thick flexible (plasterboard) partitions.

Download Technical Datasheet (PDF)
Technical Specifications
CategoryPassive Fire Protection
BrandFire Break
Shelf life12 months
Expansion Ratio19:1 (ASTM E2786-10)
Application Temperature Range+5°C to +40°C
Packaging310 ml cartridges, 600 ml foil packs, 5/10/15/19 litre containers to order
Specific gravity1,30 – 1,40
Tested floorsRigid (concrete), minimum thickness 150 mm
CertificationCE (ETA 21/0205), UL International (UL-EU-00704-CPR)
CompositionPolymer emulsion, halogen-free
Service temperature range-5°C to +70°C (indoor use, high humidity)
Storage conditionsDry place, +5°C to +35°C
Curing time3 mm/24 hours (23°C, 50% RH, depending on the gap)
Pipe diameterplastic pipes up to 160 mm
Activation temperatureapprox. 150°C
ColourGrey
Fire Resistanceup to EI 240 / E 240 (depending on the penetration type)
TypeIntumescent acrylic sealant under pressure
Reaction to fireClass E (EN 13501-1), zero flame spread (EN ISO 11925-2)
StandardsEN 13501-2, EAD 350454-00-1104 (category Y2), ISO 11600 F 7.5P
Tested wall thickness100 mm (plasterboard)
Skin time15–30 minutes (23°C, 50% RH)
Sound insulationup to 57 dB (Rw, EN ISO 10140-2)
ApplicationPlastic/metal pipes with insulation, single cables or cable bundles
VOC CategoryM1 (highest European class)