Air Conditioner ARYG72LHTA (IN) – AOYG72LRLA (OUT) 3Phase
Fujitsu

Air Conditioner ARYG72LHTA (IN) – AOYG72LRLA (OUT) 3Phase

R410A refrigerant (previous generation) — there is no equivalent R32 model in this category yet. Operating Voltage: 400 V / 50 Hz Indoor / Outdoor Unit Airflow (m³/h): 4300 / 8400 Outdoor Unit Dimensions (mm), (H x W x D): 1428 x 1080 x 480 Outdoor Unit Weight (kg): 165 Maximum Pipe Length (m): 100 Refrigerant Type / Charge: R410A / 5.6

Choose Capacity

Download Catalogue (PDF)
Technical Specifications
CategoryAir Conditioning
BrandFujitsu
Design Load Pdesign (Cooling)19,0 kW
RefrigerantR410A
Operating Range (Cooling)-15 to 46 °C
COP (Heating)3,40
Indoor Unit Weight69 kg
Heating Power Input6,59 kW
Maximum Height Difference30 m
Outdoor Unit Sound Power Level (Heating)70 dB(A)
Outdoor Unit Noise Level (Cooling)55 dB(A)
Indoor Unit Sound Power Level (Heating)79 dB(A)
Moisture Removal4,5 l/h
Outdoor Unit Airflow (Heating)8400 m³/h
Operating Range (Heating)-20 to 24 °C
Cooling Output (Cooling)19,0 kW
Outdoor Unit Airflow (Cooling)8400 m³/h
Indoor Unit Noise Level (Cooling)46 dB(A)
Outdoor Unit Weight165 kg
Static PressureHigh
Indoor Unit Dimensions (HxWxD)360 x 1400 x 850 mm
Maximum Pipe Length100 m
Indoor Unit Airflow (Heating)4300 m³/h
Heat Output (Heating)22,4 kW
Indoor Unit Airflow (Cooling)4300 m³/h
EER (Cooling)2,94
Global Warming Potential (GWP)2088
Power SupplyIndoor: single-phase 230V, 50Hz / Outdoor: three-phase 400V, 50Hz
Pipe Diameter (Liquid/Gas)12,7 / 25,4 mm
SEER (Cooling)5,22
Outdoor Unit Sound Power Level (Cooling)68 dB(A)
Pipe Length Without Additional Refrigerant30 m
Refrigerant Charge5,6 kg
Static Pressure (Adjustment Range)50 – 150 Pa (factory setting 72 Pa)
Outdoor Unit Noise Level (Heating)55 dB(A)
Indoor Unit Sound Power Level (Cooling)79 dB(A)
Design Load Pdesign (Heating)15,3 kW
Outdoor Unit Dimensions (HxWxD)1428 x 1080 x 480 mm
Indoor Unit Noise Level (Heating)46 dB(A)
Cooling Power Input6,46 kW
SCOP (Heating)3,94