LG
Air Conditioner STANDARD UV60F.N20 (IN) – UUD3.U30 (OUT) – PREMTB001 (CONTROL)
Operating Voltage: 240 V / 50 Hz Indoor/Outdoor Unit Airflow (m³/min): 30/55 Outdoor Unit Dimensions (mm), (L x H x W): 950 x 1380 x 330 Outdoor Unit Weight (kg): 85 Maximum Pipe Length (m): 85 Refrigerant Type / Charge (kg): R32/3
Choose Capacity
Download Technical Datasheet (PDF)Technical Specifications
CategoryAir Conditioning
BrandLG
Indoor/Outdoor Unit Airflow (m^3/min)30/55
Outdoor Unit Power Cable5C x 2,5 mm²
Gravity Drain Diameter (Ø ext./int.)Ø25,0 / 20,5 mm
Outdoor Unit Sound Pressure Level (Heating)54 dB(A)
Outdoor Temperature Operating Range (Heating)-25°C to 18°C
Indoor Unit Sound Power Level (Cooling)63 dB(A)
Operating Current (Heating)8,5 A
Maximum Height Difference Between Units (m)30
Pipe Connection TypeFlared
Annual Energy Consumption (Cooling)1.516 kWh
Compressor TypeInverter Scroll
Outdoor Unit Weight (kg)85
Gas Pipe DiameterØ15,88 (5/8")
Power Input (Cooling)5,33 kW (1,10-5,97)
Outdoor Unit Dimensions (mm), (L x H x W)950 x 1380 x 330
Pipe Length Minimum / Maximum (m)5 / 85
Indoor Unit Dimensions (WxHxD)1.600 x 235 x 690 mm
Minimum Outdoor Unit Fuse Rating (A)20
Dehumidification Rate (l/h)7,1
Outdoor Unit Sound Power Level (Cooling)71 dB(A)
Indoor Unit Airflow (High/Medium/Low)30/25/20 m³/min
Operating Current (Cooling)8,2 A
EER2,70
Power Input (Heating)5,60 kW (1,10-6,44)
Cooling Output (Cooling)14,4 kW (5,8-15,6)
SCOP4,1
Outdoor Unit Sound Pressure Level (Cooling)54 dB(A)
Refrigerant - DetailsR32, GWP 675, 3,0 kg (2,025 t CO2eq)
Operating Voltage240 V/ 50 Hz
COP3,00
Indoor Unit Weight36,7 kg
Indoor Unit Power Input (High/Medium/Low)59/40/28 W
Indoor Noise Level (High/Medium/Low)48/44/40 dB(A)
Indoor Unit Power Supply1~ / 220-240 V / 50 Hz
Annual Energy Consumption (Heating)3.244 kWh
Heat Output (Heating)16,8 kW (6,7-18,1)
Refrigerant Type / Charge (kg)R32/3
Outdoor Temperature Operating Range (Cooling)-20°C to 52°C
Additional Refrigerant (g/m)40 g/m (beyond 7.5 m)
Outdoor Unit Fan (m³/min × number)55 x 2
Maximum Pipe Length (m)85
SEER5,7
Pumped Drain Diameter (Ø ext./int.)Ø32,0 / 26,0 mm
Liquid Pipe DiameterØ9,52 (3/8")
Pdesign (Heating)9,5 kW (-10°C)
Pdesign (Cooling)14,4 kW (35°C)