Actionair
SMOKE COMMAND MCD
SMOKE COMMAND MCD is a multi-blade smoke control damper, CE-marked with an ES classification, for automatic activation (AA) systems. It is intended for smoke extraction networks serving one or more fire compartments, as well as for combined smoke and environmental ventilation systems. Its HOT 400/30 classification allows it to cycle and adjust its position for 30 minutes at 400°C.
Download Technical Datasheet (PDF)Technical Specifications
CategoryPassive Fire Protection
BrandActionair
SealsHigh-temperature silicone, synthetic gaskets, perimeter seal
Casing material1.2 mm galvanised sheet steel, double-skin, fully welded per BS EN 10142
Blade Depth81.5 mm, double-skin, with high-temperature silicone
Size Range200x200 mm to 1000x1000 mm (in 1 mm steps in width and height)
WiringHalogen-free low smoke (FP200 GOLD), 1 metre tail
Maximum System Pressure1000 Pa
Weight (square, without actuator)<200 mm: 3.4 kg · 400 mm: 6.5 kg · 600 mm: 10.8 kg · 800 mm: 16.2 kg · 1000 mm: 23.5 kg (+13 kg for actuator/thermal casing)
Maximum Air Velocity15 m/s
Installation methodsDWFX-F (1.2 mm flange with 50 x 50 mm angles and 14 x 24 mm oval holes) in solid walls and plasterboard
Running Time<60 seconds (open/close)
CertificationCE marking
Blade depth81.5 mm, aerodynamic double-skin with interlocking
ClassificationES (integrity and low smoke leakage)
ActuatorsSCHM5-2P PTC: 24V AC/DC 50/60Hz (8W max) · SCHM6-2P PTC: 230V AC 50/60Hz (12W max) · IP54, 2 separate volt-free contacts
Operating Pressure Range-1000 to +500 Pa
StandardsEN 12101-8, EN 1366-10, EN 1366-2, EN 13501-4
Free area retainedOver 120 minutes at elevated temperatures
InstallationDWFX-F: 1.2 mm galvanised steel frame with 50x50 mm angles and 14x24 mm oval holes
Duct connectionSquare or rectangular, with spigots
TypeMulti-blade smoke control damper (AA - automatic activation)
Control compatibilityACTIONPAC damper control panels
Acoustic DataSound power level charts (Velocity × Pressure Drop) with octave-band spectrum corrections (63–8000 Hz) for outlet and casing-radiated noise
Installation Wall ThicknessUp to 250 mm (PTC interface)
Thermal CasingLightweight material with endothermic properties, extends actuator operation at high temperatures
Blade materialFerritic stainless steel 430 (1.4016) per BS EN 10088-2; optionally 316 (1.4401)
Thermal classHOT 400/30 — cycling and position control for 30 minutes at 400°C
Casing tightnessEurovent Document 2/2 classes A and B; HVCA DW144 classes A, B and C
MotorTwo-position (drive open / drive close), chosen according to the project requirements