SMOKESHIELD
Actionair

SMOKESHIELD

SMOKESHIELD is a multi-blade automatic fire damper, CE-marked with an ES classification, for square, rectangular or circular ducts. It restores fire compartmentation in the event of a fire, preventing the spread of fire and smoke. It closes either via the building's automatic fire detection system or via a local 72°C thermal release.

Download Technical Datasheet (PDF)
Technical Specifications
CategoryPassive Fire Protection
BrandActionair
Control compatibilityActionpac damper control system
CertificationCE marking
Maximum Air Velocity15 m/s
Blade sealsSynthetic, with steel end bearings and perimeter gasket
Flow DirectionIn both directions
Thermal Release (BAT)72°C or power failure, per BS 9999:2017
TypeMulti-blade automatic fire damper (SmokeShield PTC)
Acoustic DataPressure drop–velocity and sound power level charts with octave-band spectrum corrections (Series 501/601) for outlet and casing-radiated noise
Installation methodsDWFX-F, DWFX-C, S&A (Sleeve & Angle with ablative batt), SPAN — concrete/masonry, plasterboard and composite wall systems
Casing Thickness1.2 mm galvanised steel (BS EN 10346:2009)
Dimension Range100x100 mm to 1000x1000 mm (in 1 mm steps in width and height)
WeightWithout actuator (square); +4.4 kg for the actuator
Size rangeWide range, with multiple banks possible for large-section ducts
CasingFully welded, 1.2 mm galvanised steel, with connection spigots
MotorsChoice of motors according to project requirements
WiringHalogen-free, low smoke and fume
Fire resistance classificationES (integrity and low smoke leakage)
BladesAerodynamic interlocking, opposed blade, 75 mm, stainless steel
Test Cycles10,000 cycles
Duct connectionSquare, rectangular or circular
ActuationBuilding automatic fire detection system or local thermal release at 72°C
Maximum System Pressure1500 Pa
ActuatorsM5 PTC 24V (10/2 W, 12.5 VA) · M6 PTC 230V (12/4 W, 14 VA) · a third type with volt-free contacts is also available
Duct tightnessClasses A and B per Eurovent Document 2/2; classes A, B and C per HVCA DW144
Operating Time60 s drive to end position, 22 s spring return
StandardsEN 15650, EN 1366-2, EN 13501-3