Actionair
THERMSHIELD FD
THERMSHIELD FD is a single-blade fire damper, CE-marked with an EIS classification, with mechanical or automatic operation. It prevents the spread of fire and smoke, maintaining fire compartmentation in internal dry filtered air systems. Its calcium silicate blade also provides thermal insulation, in addition to integrity and smoke tightness.
Download Technical Datasheet (PDF)Technical Specifications
CategoryPassive Fire Protection
BrandActionair
Mechanical operationThermal release activating at 72°C
Fire resistance classificationEIS (integrity, insulation, low smoke leakage)
BearingsBrass
StandardsEN 15650, EN 1366-2, EN 13501-3, EN 1751
WeightFD-R: 5.0 kg (100x200) to 67.1 kg (1500x800); EMS-S +2.2 kg, EX +4.6 kg
Installation methodsStandard, applique, MF2 and remote
Maximum system pressure1000 Pa
Pressure DropΔp = ζ · v² · 0.6 with Zeta values per size (manufacturer's tables)
FD40 size range850x650 to 1500x800 mm
Blade materialCalcium silicate
LeakageClass 2 (closed blade), class C (casing) per EN 1751
Maximum Air Velocity (actuators)Electric up to 12 m/s, EMS up to 10 m/s, manual <10 m/s
CertificationCE marking
Maximum air velocity12 m/s
Casing materialGalvanised sheet steel (also available in stainless steel or with electrostatic paint)
FD25 size range100x200 to 800x600 mm
Auto modeSafety spring with fail-safe closing
Mounting PositionVertical or horizontal blade axis
Installation ClassificationEI 60/90/120 (ve, ho, i↔o) S depending on wall/floor type and installation method; Applique and MF2 up to EI90S
Operating Temperature Range-20°C to 50°C
HygieneTested by the Institute of Hygiene (Gelsenkirchen), VDI 6022 compliant — suitable for hospitals, clinics and pharmaceutical facilities
SealsPolyurethane and elastomeric rubber
Environmental DeclarationEPD (EN 15804+A2, ISO 14025)
Casing Length350 mm
ATEX versionII 2G Ex h IIC T6 Gb / II 2D Ex h IIIC T80°C Db (FIDI 21 ATEX D059), Schischek ExMax-5.10-BF actuator
Activation Temperature72°C (standard) or 95°C (optional, with electric actuator)
TypeSingle-blade fire damper, mechanical or automatic operation