THERMSHIELD FDC
Actionair

THERMSHIELD FDC

THERMSHIELD FDC is a circular single-blade fire damper, CE-marked with an EIS classification, with mechanical or automatic operation. It restores fire compartmentation in ventilation systems with circular ducts, preventing the spread of fire and smoke. It covers diameters from 100 to 800 mm and is available with a manual or electric actuation mechanism.

Download Technical Datasheet (PDF)
Technical Specifications
CategoryPassive Fire Protection
BrandActionair
Net Free Area (dm²)0.50 (Ø100) to 46.68 (Ø800)
TypeCircular single-blade fire damper, mechanical or automatic operation
Maximum air velocity12 m/s
Cross-Section (dm²)0.74 (Ø100) to 49.86 (Ø800)
Operating Temperature Range-20°C to 50°C
Control compatibilityActionpac damper control system
ATEX versionII 2G Ex h IIC T6 Gb / II 2D Ex h IIIC T80°C Db (FIDI 21 ATEX D059), Schischek ExMax-5.10-BF actuator
Maximum Air Velocity (actuators)Electric up to 12 m/s, EMS up to 10 m/s
Mechanism positionOut of the airstream
Casing materialGalvanised sheet steel (also available in stainless steel or with electrostatic paint)
CertificationCE marking
Pressure DropΔp = ζ · v² · 0.6 — ζ: FDC25 Ø100 1.759 / Ø125 0.852 / Ø160 0.545 / Ø200 0.445 / Ø250 0.340 / Ø315 0.293 · FDC40 Ø355 0.428 / Ø400 0.389 / Ø450 0.344 / Ø500 0.325 / Ø560 0.312 / Ø630 0.232 / Ø710 0.206 / Ø800 0.179
Mounting PositionVertical or horizontal blade axis (axis angle 0–360°)
StandardsEN 15650, EN 1366-2, EN 13501-3, EN 1751
Maximum system pressure1000 Pa
Installation methodsStandard, Applique, MF1/MF2 and Remote — concrete/masonry and plasterboard, including installation away from the wall
LeakageClass 2 (closed blade), class C (casing) per EN 1751
FDC25 diameter range100 to 315 mm
Casing Length380 mm
Manual operationSpring-return mechanism and thermal release at 72°C
HygieneTested by the Institute of Hygiene (Gelsenkirchen), VDI 6022 compliant — suitable for hospitals, clinics and pharmaceutical facilities
SealsPolyurethane and elastomeric rubber
FDC40 diameter range355 to 800 mm
Duct connectionCircular
Auto modeSpring-return motor, fail-safe closed
Environmental DeclarationEPD (EN 15804+A2, ISO 14025)
Blade materialCalcium silicate
Activation Temperature72°C (standard) or 95°C (optional, with electric actuator)
Fire resistance classificationEIS (integrity, insulation, low smoke leakage)
BearingsBrass