Technical Specifications
CategoryHeat Pumps & Fan Coils
BrandLG
Heating COP at -7°C2.80 (A-7/W35) / 2.40 (A-7/W55)
Outdoor UnitHM073HF UB40
Heating SCOP (55°C water)3.86
PhaseThree-phase
Water Pipe ConnectionsMale PT 1" (ISO 7-1)
Outdoor Temperature Operating Range (Heating)-28°C to 35°C
Heating Energy Class (35°C)A+++
Heat Output (kW)7.00 kW (A7/W35) / 4.50 kW (A7/W55) / 7.00 kW (A2/W35)
Supply Water Temperature Range (Cooling)5°C to 27°C
Refrigerant - DetailsR290, GWP 3, 0.9 kg (0.0027 t CO2eq)
Outdoor Unit Sound Power Level - Low Noise (dB)48
Cooling Output (kW)5.00 kW (A35/W18) / 5.00 kW (A35/W7)
Cooling EER4.40 (A35/W18) / 2.80 (A35/W7)
Seasonal Heating Efficiency ηs (35°C water)207 %
Heating Energy Class (55°C)A+++
Outdoor Temperature Operating Range (Cooling)5°C to 48°C
Heat Output at -7°C (kW)7.00 kW (A-7/W35) / 7.00 kW (A-7/W55)
Electrical Characteristics3~/50Hz/380-415V
Outdoor Unit Weight (kg)130.0
Indoor UnitCombi Unit
Outdoor Unit Sound Power Level LW(A) (dB)49
Heating SCOP (35°C water)5.24
Maximum Supply Water Temperature (°C)75 °C (according to the indoor unit table)
RefrigerantR290
Standby Consumption (W)10
Outdoor Unit Sound Pressure Level (dBA)27 (at 5 m)
Seasonal Heating Efficiency ηs (55°C water)151 %
Recommended Circuit Breaker (A)16
Heating COP5.00 (A7/W35) / 3.35 (A7/W55) / 3.80 (A2/W35)
Capacity (kW)7 kW
Supply Water Temperature Range (Heating)15°C to 75°C (according to the indoor unit table)
Outdoor Unit Sound Pressure Level - Low Noise (dBA)26 (at 5 m)
Measurement ConditionsA: outdoor air temperature, W: leaving water temperature (LWT)
Outdoor Unit Dimensions (HxWxD mm)1019 x 1320 x 520