← LG THERMA V R290 Monobloc
LG THERMA V R290 Monobloc HM121HF UB60
LG

LG THERMA V R290 Monobloc HM121HF UB60

LG THERMA V (R290 Monobloc) air-to-water heat pump, 12kW, single-phase. Refrigerant R290.

Choose Capacity

Download Catalogue (PDF)
Technical Specifications
CategoryHeat Pumps & Fan Coils
BrandLG
Cooling EER3.78 (A35/W18) / 3.12 (A35/W7)
Outdoor Unit Weight (kg)181.0
Measurement ConditionsA: outdoor air temperature, W: leaving water temperature (LWT)
Heating COP at -7°C3.27 (A-7/W35) / 2.32 (A-7/W55)
Cooling Output (kW)11.50 kW (A35/W18) / 10.50 kW (A35/W7)
Seasonal Heating Efficiency ηs (55°C water)156 %
PhaseSingle-phase
Heating Energy Class (35°C)A+++
Outdoor Unit Sound Power Level - Low Noise (dB)48
Heating SCOP (35°C water)5.45
Heating SCOP (55°C water)3.97
Capacity (kW)12 kW
Heat Output (kW)12.00 kW (A7/W35) / 10.00 kW (A7/W55) / 12.00 kW (A2/W35)
Seasonal Heating Efficiency ηs (35°C water)215 %
Domestic Hot Water Seasonal Efficiency ηwh (profile L)130 %
Water Pipe ConnectionsMale PT 1" (ISO 7-1)
Outdoor Unit Sound Power Level LW(A) (dB)49
Heating COP4.70 (A7/W35) / 3.10 (A7/W55) / 3.72 (A2/W35)
Heat Output at -7°C (kW)11.80 kW (A-7/W35) / 9.30 kW (A-7/W55)
Outdoor Unit Dimensions (HxWxD mm)1019 x 1560 x 520
Supply Water Temperature Range (Heating)15°C to 75°C (according to the indoor unit table)
Recommended Circuit Breaker (A)25
RefrigerantR290
Outdoor Temperature Operating Range (Cooling)5°C to 48°C
Indoor UnitCombi Unit
Supply Water Temperature Range (Cooling)5°C to 27°C
Outdoor UnitHM121HF UB60
Maximum Supply Water Temperature (°C)75 °C (according to the indoor unit table)
Refrigerant - DetailsR290, GWP 3, 1.2 kg (0.0036 t CO2eq)
Heating Energy Class (55°C)A+++
Electrical Characteristics1~/50Hz/220-240V
Standby Consumption (W)10
Outdoor Unit Sound Pressure Level - Low Noise (dBA)26 (at 5 m)
Outdoor Temperature Operating Range (Heating)-28°C to 35°C
Outdoor Unit Sound Pressure Level (dBA)27 (at 5 m)